Synthetic resin insulated wire
KIV/HKIV/USH-KIV/125-KIV
Synthetic resin insulated wire
【feature】
●Used for wiring electrical equipment below 600V.
●Conductors are available in annealed copper stranded wires and tin-plated annealed stranded copper wires.
KIV
【feature】
Voltage:600V
temperature:60℃
HKIV
【feature】
Voltage:600V
temperature:75℃
USH-KIV
【feature】
Voltage:600V
temperature:105℃
125-KIV
【feature】
Voltage:600V
temperature:125℃
conductor | vinyl insulator | |||
---|---|---|---|---|
nominal cross-sectional area(㎟) | composition( /㎜) | outer diameter(㎜) | thickness(㎜) | outer diameter(㎜) |
0.75 | 30/0.18 | 1.1 | 0.8 | 2.7 |
1.25 | 50/0.18 | 1.5 | 0.8 | 3.1 |
2.0 | 37/0.26 | 1.8 | 0.8 | 3.4 |
3.5 | 45/0.32 | 2.5 | 0.8 | 4.1 |
5.5 | 70/0.32 | 3.1 | 1.0 | 5.1 |
8.0 | 50/0.45 | 3.7 | 1.2 | 6.1 |