1. HOME
  2. HOME_eng
  3. Product
  4. Electric wire
  5. Power cable
  6. Vinyl insulated wire for lead-in

Vinyl insulated wire for lead-in
DV2R/DV3R/DV2F/DV3F

Vinyl insulated wire for lead-in


【feature】
●Used for overhead service lines of 600V or less.
Conductors are available in hard copper wire and annealed copper wire depending on size.

電子機器用ビニル電線

DV2R (2 strands)

【Rated】
Voltage:600V
temperature:60℃
JIS certification number:JE0507022

DV3R (3 strands)

【Rated】
Voltage:600V
temperature:60℃
JIS certification number:JE0507022

DV2F (2-core flat)

【Rated】
Voltage:600V
temperature:60℃
JIS certification number:JE0507022

DV3F (3-core flat)

【Rated】
Voltage:600V
temperature:60℃
JIS certification number:JE0507022

 

 

DV2R

conductor vinyl insulator finish
nominal cross-sectional area
(㎟)
composition
( /mm)
outer diameter
(mm)
thickness
(mm)
outer diameter
(mm) 
outer diameter
(mm) 
1/2.0 2.0 0.8 3.6 7.2
1/2.6 2.6 1.0 4.6 9.2
1/3.2 3.2 1.2 5.6 11.2
8 7/1.2 3.6 1.2 6.0 12.0
14 7/1.6
4.8 1.4 7.6 15.2
22 7/2.0
6.0 1.6 9.2 18.4
38
7/2.6
7.8 1.8 11.4 22.8
60 19/2.0
10.0
1.8 13.6 27.2
100 19/2.6 13.0 2.0 17.0 34.0

 

 

DV3R

conductor vinyl insulator finish
nominal cross-sectional area
(㎟)
composition
( /mm)
outer diameter
(mm)
thickness
(mm)
outer diameter
(mm)
outer diameter
(mm)
1/2.0 2.0 0.8 3.6 7.8
1/2.6 2.6 1.0 4.6 9.9
1/3.2 3.2 1.2 5.6 12.1
8 7/1.2 3.6 1.2 6.0 12.9
14 7/1.6
4.8 1.4 7.6 16.4
22 7/2.0
6.0 1.6 9.2 19.8
38
7/2.6
7.8 1.8 11.4 24.6
60 19/2.0
10.0
1.8 13.6 29.3
100 19/2.6 13.0 2.0 17.0 36.6

 

 

DV2F DV3F

number of cores conductor vinyl insulator
outer diameter
(mm)
thickness
(mm)
outer diameter
(mm)
2 cores 2.0 0.8 3.6×8.4
2.6 1.0 4.6×10.4
3.2 1.2 5.6×12.4
3 cores 2.0 0.8 3.6×12.7
2.6 1.0 4.6×15.7
3.2 1.2 5.6×18.7
※The items marked with * are annealed copper wires.

 

 

 

〇In addition to the above, we will design and manufacture various special specifications upon request.〇